OptiPlant AI
3 DCS
Portal:Governance & Model Ops/Audit & Model Ops
Total AI Decisions (90 d)

58,412

Fully traceable, immutable log

HITL / Rejections / Auto

4,218 / 612 / 53,582

Approvals β€’ Rejections β€’ Autopilot

Exports This Quarter

12

21 CFR Part 11 + ISO 27001

Models Prod / Shadow / Retired

7 / 3 / 14

Registry managed

Audit Trail

TimestampActorActionTargetBefore β†’ AfterJustificationMode
2026-04-21 14:27:33AI (Paint-Quality v2.3) β†’ J.Novak approved
SP change
SP_pH5.80 β†’ 5.72 pH-3.2% defect rate forecast, conf 92%
HITL
2026-04-21 14:23:47Autopilot
SP change
SP_Pressure7.20 β†’ 6.80 bar-3.6% comp kW, conf 90%, within guardrails
AUTOPILOT
2026-04-21 14:19:11J.Novak
Alarm ack
Cure Oven Z2 high tempβ€”ack + comment "Reducing SP to 173Β°C"
HITL
2026-04-21 14:18:05System
WO created
WO-10254 AC-03 bearingβ€”Auto-created from RUL<14d
2026-04-21 14:08:22J.Novak (HITL approve)
SP change
Formation03 ChargeRate0.33C β†’ 0.38C+4.1% throughput, conf 86%
HITL
2026-04-21 13:54:58M.Okafor
Guardrail edit
Max deviation4% β†’ 5%Pilot program expansion
HITL
2026-04-21 13:40:12J.Novak
SP change
Cure Oven Z2 SP172 β†’ 175 Β°CCompensating for new body style Zeta
HITL
2026-04-21 12:05:49Autopilot
SP revert
Boiler Oβ‚‚ trim2.6% β†’ 3.0%Post-write rollback, PV violated 3Οƒ within 10 min
AUTOPILOT
2026-04-21 11:42:00AI + J.Novak reject
SP rejected
Phosphate BathTemp 54β†’53β€”Wait for weekly oven PM (operator)
HITL
2026-04-21 10:19:14System
Model promotion
Paint-Quality v2.3 β†’ prodβ€”Challenger gate passed 7 days RΒ²>0.88
2026-04-21 08:12:41Autopilot
SP change
AHU-Paint supply14.0 β†’ 16.0 Β°C-260 kWh/day, conf 89%
AUTOPILOT
2026-04-20 22:14:07S.Hartley
Guardrail edit
Safety-excluded tag addedβ€”Quarterly safety review β€” added ns=2;s=PA.Safety.InterlockBypass
HITL
2026-04-20 18:03:22Autopilot
SP change
Chiller01 SP_SupplyTemp6.5 β†’ 7.2 Β°C-4.1% kW, conf 94%
AUTOPILOT
2026-04-20 17:41:55System
Data ingest
Feature store refresh47 tagsScheduled 5-min cycle
2026-04-20 16:27:10O.Park
WO assigned
WO-10248 Comp-air leakβ€”Leak kit ready β€” assigned to Team 7
HITL

Model Registry

Compliance Exports

21 CFR Part 11 Audit
ISO 27001 quarterly
Internal eng. review

Recent Exports

2026-04-21 14:27audit-2026-04-21-1427.zip12.4 MB
2026-04-14 09:00audit-2026-04-14-0900.zip11.8 MB
2026-04-07 09:00audit-2026-04-07-0900.zip10.2 MB
2026-03-31 09:00audit-2026-03-31-0900.zip9.8 MB
2026-03-24 09:00audit-2026-03-24-0900.zip10.6 MB

Autopilot Governance

HITL MODE
Max Β±5% SP deviation
Max 3 adj/unit/hr
No shift-handover writes
Safety tags excluded (8)
Rollback on 3Οƒ violation
Confidence β‰₯ 80%

Recent Autopilot Actions

14:23:47CompAir SP 7.20β†’6.80 bar
12:05:49Boiler Oβ‚‚ trim reverted 2.6%β†’3.0%
08:12:41AHU-Paint 14β†’16Β°C
2026-04-20 18:03Chiller01 SP 6.5β†’7.2Β°C
2026-04-20 14:44E-Coat Voltage 285β†’282V
2026-04-20 12:18Spray Booth AirFlow 12400β†’12800